Fire Pumps and Fixed Systems in the Engine Room
The emergency fire pump is designed to work precisely when the main engine room is inaccessible: its maintenance therefore requires a discipline independent from that of the main machinery.
Operational Explanation
The main fire pumps and the emergency fire pump form the basic water system for onboard firefighting. The emergency pump is specifically designed to remain operative even when the main engine room is inaccessible (e.g. due to fire in the engine room itself), which requires an independent location and power supply, as well as dedicated maintenance.
Fixed extinguishing systems in the engine room (CO2, foam, water sprinkler) complete the protection, but require specific periodic checks, distinct from routine machinery maintenance.
Regulatory Reference
SOLAS Chapter II-2, Regulation 10 (Fire fighting): requirements on the number and capacity of fire pumps, required pressure at hydrants, and characteristics of the emergency fire pump, which must be located outside the main machinery space with an independent power supply.
Regulation 10 is extinction; Regulation II-2/4 is prevention, and the two must be read together because in almost every machinery space fire the fuel is oil. Paragraph 4.2.2.3.4 requires, on every storage, settling or daily service tank having a capacity of 500 l and above situated above the double bottom, “a cock or valve directly on the tank capable of being closed from a safe position outside the space concerned in the event of a fire occurring in the space in which such tanks are situated”: these are the quick-closing valves, and testing them belongs to the same routine as testing the emergency fire pump, because they serve the same scenario — a space abandoned and no longer accessible. Paragraph 4.2.2.6.1 adds that surfaces above 220 °C exposed to a fuel leak must be insulated: oil-soaked lagging over an exhaust manifold is the most frequent ignition source. See the Bunkering Operations entry for the full picture of Regulation II-2/4.
The figures in Regulation 10.2, which this page did not carry. 10.2.2.2 sets how many independently driven pumps are required: three on passenger ships of 4,000 GT and upwards, two below that; two independently driven on cargo ships of 1,000 GT and upwards, and below 1,000 GT two power-driven pumps of which at least one independently driven. 10.2.1.6 sets the minimum pressure to be maintained at all hydrants with two pumps delivering simultaneously: 0.40 N/mm² on passenger ships of 4,000 GT and upwards, 0.30 below; 0.27 on cargo ships of 6,000 GT and upwards, 0.25 below. Note that SOLAS states these in N/mm², not bar: 0.40 N/mm² is 4 bar.
10.2.1.3 requires the fire main diameter to be sufficient for the maximum discharge of two pumps operating simultaneously, with the derogation for cargo ships where 140 m³/h suffices; 10.2.2.4 provides that the total capacity of fire pumps on cargo ships need not exceed 180 m³/h. The emergency fire pump is sized in the FSS Code, Chapter 12, paragraph 2.2.1.1: not less than 40% of the total capacity of the main fire pumps, and in any case not less than 25 m³/h for cargo ships of 2,000 GT and upwards and passenger ships below 1,000 GT, 15 m³/h for cargo ships below 2,000 GT.
The testing intervals are not in SOLAS, and that generates the commonest error. Regulation II-2/14 says only that systems be kept in good working order and that maintenance, testing and inspections be carried out “based on the guidelines developed by the Organization”, with the maintenance plan kept on board for inspection. The intervals are in MSC.1/Circ.1432, as amended by MSC.1/Circ.1516. For pumps: a monthly operational test of all pumps, confirming they continue to supply adequate pressure, plus a monthly check of the emergency pump's fuel supply and heating; an annual flow test of all pumps, with the emergency pump tested with isolation valves closed, relief valves properly set and strainers cleaned. The circular does have a weekly section, §4, and it is worth saying what is in it, because that is where the confusion starts: fire detection panels, fixed gas system panels and valve positions, fire door panels, public address and general alarm systems, breathing apparatus and EEBD gauges, low-location lighting, and the panels and pump unit of the water mist/sprinkler system (§4.7.2). Fire pumps are not among the weekly items: they sit at §5.1 (monthly) and §7.1 (annual). The only weekly “pump” is the sprinkler one, which is a different system. Anyone running a weekly test of the emergency fire pump is doing so under a Company procedure, a class rule or a flag requirement, not under this circular: it is worth knowing which of the two you are demonstrating to an inspector.
Scope of Application
Every ship subject to SOLAS Chapter II-2, with specific requirements on the minimum number of fire pumps depending on ship type and size.
Procedure / How to Complete It
- Periodically test the main fire pumps, verifying pressure and flow at the most unfavourable hydrants.
- Separately test the emergency fire pump, verifying independent start-up and the ability to operate with the main engine room hypothetically inaccessible.
- Periodically verify fixed extinguishing systems (CO2, foam, sprinkler) according to manufacturer instructions and Class requirements.
- Record every test and maintenance activity, with particular attention to anomalies found on the emergency pump.
- Coordinate fire pump tests with periodic fire drills, to verify actual availability in a realistic operational scenario.
Practical Example
Example test: emergency fire pump started monthly independently from the main power supply, with pressure verified at the furthest deck hydrant, result recorded in the engine log book.
What Typically Goes Wrong
Common Mistakes Mistake Library
| Mistake | Consequence | How to avoid it |
|---|---|---|
| Emergency pump test conducted using the same power supply as the main engine room | The test does not genuinely verify the emergency condition the pump is designed for | Test the emergency pump in its actual independent power supply configuration |
| Hydrant pressure verified only at the point nearest the pump | Pressure shortfall at the most unfavourable points not detected | Also verify pressure at the furthest/most unfavourable hydrants of the system |
| Fixed extinguishing systems (CO2, foam) checked less frequently than water pumps | Malfunction of the fixed system discovered only in a real emergency | Include fixed systems in an equally rigorous periodic verification programme |
What the PSCO Checks
Operational Tips
- Always test the emergency pump in its genuinely independent power supply configuration, not with operational shortcuts.
- Verify pressure at the most unfavourable hydrants of the system, not only those nearest the pump.
- Do not neglect fixed extinguishing systems when planning periodic checks.
Preparation checklist
Educational checklist. This summary supports learning and preparation only. It does not replace the vessel’s approved procedures, manuals, statutory documents, company SMS, or applicable official requirements. Completing it demonstrates neither compliance nor readiness for an inspection: it shows that a list has been read, not that the ship is in order. Always verify the current documents carried on board.
- Main fire pumps tested with pressure/flow verification
- Emergency fire pump tested in genuinely independent configuration
- Fixed extinguishing systems verified according to manufacturer instructions
- Tests coordinated with periodic fire drills
- Anomalies on the emergency pump recorded and resolved with priority
FAQ
Related Topics
Last substantive revision of this page: 19 August 2026 · page fingerprint b3320eac5671